
O.M.I.A.
FAQ
FAQ 1. Can duct coverings penetrate a wall or floor required to be fire blocked if the covering and all materials are non-flammable or combustible?
Answer - Section 604.6 of the International Mechanical Code addresses
penetrating a wall required to be fire blocked. It states that "Duct
coverings shall not penetrate a wall or floor required to have a fire
resistance rating or required to be fire blocked." Be sure to check with
your local AHJ (Authority Having Jurisdiction) about your community
application of this rule.
FAQ 2. Refrigerants must be classified as to high and low probability systems. What factors are considered in making these determinations?
Answer - Section 1103 covers Refrigerant Classification and says that High
or Low will be based upon the potential hazard resulting from
leakage or refrigerant into an occupancy classified area other
than the machinery room. Examples of this consideration would be
direct, indirect open spray indirect closed etc.... being Low.
If you are not familiar with these systems post a question with our
discussion group.
FAQ 3. I do not have enough room on the roof to get the ten-foot separation between a source of contaminants and a fresh air inlet opening. What are my options for compliance?
Answer - Section 401.5 governs opening locations and it essentially says that
all contaminant sources shall be at least ten (10) feet away,
horizontally, or they must terminate at a point not less than two (2) feet
above the Outside air inlet. I initially said be raised to but the inlet
opening could also be lowered, the critical issue is a two (2) foot
vertical separation.
FAQ 4. What is the function of a duct smoke detector with respect to controls?
Answer - Section 606.4 states that "upon activation the smoke detectors shall
shut down the air distribution system. One of the common
misconceptions is that a time delay is acceptable in shutting the air
system down, the code states "upon activation". This is a life safety
provision of the code to prevent the distribution of smoke
contaminated air.
FAQ 5. Do I need a smoke detector if a unit on a commercial application has 2000 cfm
maximum supply?
Answer - Section 606.2.1 requires that a smoke detect be installed in return air
systems if the DESIGN capacity is greater than 2000 CFM. In your
instance the critical question is the design of the return air system not
the capacity of the equipment. With an eye to the fact that the building
will probably outlast the equipment and a replacement unit will have to
be installed, it is the capacity of the duct system that is a concern.
Please check with the AHJ in your location.
FAQ 6. Can removal of flex duct from a fire damper be permitted as access to the
damper? What type of marking if any is needed?
Answer - Section 607.4 does not specifically address flex duct however, the
methods of attachment for flex duct does not provide an effective
means to routinely and regularly remove and reattach the duct. If a
system is a flexible duct system and contains a fire damper, a rigid
permanently attached duct connector with an access door would be
required between the flex duct and the fire damper. The connector
would have to be large enough to permit inspection and maintenance
access to the damper and its operating parts. This same section
required a label with the marking not less than 1/2 inch in height that
reads SMOKE DAMPER or FIRE DAMPER
FAQ 7. Where do I install the smoke detectors, in the supply or return air?
Answer - Section 606.2.1 says smoke detectors shall be installed in the return
air system when required. This does not restrict additional smoke
detectors being added in addition to the required detectors.
FAQ 8. Does the ceiling of my furnace closet need to be sealed or can I use
combustion air from the attic with an open ceiling?
Answer - Chapter 7 governs the rules for combustion air and combustion
air continues to be an area that generated many questions. Section
701.4 tells us that the attic air can be considered outside air if the
attic is ventilated to provide air equal to that required for ventilation and
combustion. Again better check with the AHJ